7 position - time (pt), Position - time (pt) -21 – ElmoMC SimplIQ Software Manual User Manual

Page 162

Advertising
background image

SimplIQ

Software Manual

The Position Reference Generator

MAN-SIMSW (Ver. 1.4)

11-21

The following CAN emergencies are supported:

Error
Code
(Hex)

Error
Code
(Dec)



Reason



Data Field

0x56

86

Queue is low. Number of yet
unexecuted PVT table rows has
dropped below the value stated in
MP[4].

Field 1: Write pointer
Field 2: Read pointer

0x5b

91

Write pointer is out of physical range
([1…64]) of PVT table. Reason may be
an improper setting of MP[6].

Value of MP[6]

0x5c

92

PDO 0x3xx is not mapped.

0x34

52

An attempt has been made to program
more PVT points than are available in
queue.

Field 1: Index of PVT table
entry that could not be
programmed

0x7

7

Cannot initialize motion due to bad
setup data. The write pointer is outside
the range specified by the start and end
pointers.

0x8 8 Mode

terminated and motor has been

automatically stopped (in MO=1).

Data field 1: Write pointer

Data field 2:
1: End of trajectory in non-
cyclical mode
2: A zero or negative time
specified for a motion
interval
3: Read pointer reached
write pointer

0x9

9

A CAN message has been lost.

Figure

11-8: PVT CAN Emergency Messages

11.1.7 Position - Time (PT)

In a PT motion, the user specifies a sequence of absolute positions with equal time spaces
to be visited by the drive. The time space must be an integer multiple of the drive
sampling time. Between the user-specified positions, the drive interpolates smooth
motion. The position specifications are absolute.