2 stop manager internal elements, Stop manager internal elements -41, Simpliq – ElmoMC SimplIQ Software Manual User Manual

Page 182

Advertising
background image

SimplIQ

Software Manual

The Position Reference Generator

MAN-SIMSW (Ver. 1.4)

11-41

ƒ

Limits the magnitude of the controller command to the maximum allowed range.
This is necessary because even if the software command is generated within the
permitted limits and the external command is also within the permitted limits, their
total value may exceed the permitted limits.

The stop manager prevents the position reference generator from driving the motor to
undesired positions. It does not affect the reference generator.

The commands relevant to the stop manager are:

Command Description

SD

Maximum rate that the motor can accelerate/decelerate

IL[N]

Input logic: define the functions associated with the digital inputs

VH[N], VL[N] Maximum allowed controller command

XM[N], YM[N] Modulo count for main and auxiliary sensors

Table

11-11: Stop Manager Commands

11.3.2 Stop Manager Internal Elements

The stop manager is depicted in the following diagram:

Position

command

(Software and

External)

Clip Position command

to range

Select zero if

hard-stop

Prevent backwards motion

Select

direction limit

if RLS

Select

direction limit

if FLS

Prevent Forward Motion

Rate &

Acceleration

limiter

Position command to

motion controller

1

2

3

4

5

Figure

11-18: Stop Manager Block Diagram