Function library "LenzeIo1000Drv"

Function blocks

L_io1000ParAiTemperature - Parameterise temperature measurement

Inputs

Identifier/data type

Information/possible settings

bExecute

BOOL

FALSEÊTRUE Start parameter setting of the analog input module

dwHandle

DWORD

• 9400 ServoPLC: Handle created by FB L_CanInit

• Drive PLC, 9300 Servo PLC, ECS: 10

byNodeAdr

BYTE

1 ... 127 CAN node address of the I/O system

byAnalogModuleNo

BYTE

1 ... 64 Number of the analog input module

byNoOfChannels

BYTE

Number of channels of the I/O system

2 EPM-S405
4 EPM-S404

bDiagnosticAlarm

BOOL

TRUE Enable diagnostic alarm

byTemperatureSystem

BYTE

Temperature system

0 °C
1 °F
2 K

byFilter

BYTE

Activate interference frequency suppression

1 60 Hz
2 50 Hz

bWireBreakDetection

_CH1 ... _CH4

BOOL

TRUE Activate open circuit detection channel 1 ... 4

byFunction_CH1 ... _CH4

BYTE

Function channel 1 ... 4

• see system manual "I/O system 1000":

EPM-S404: Chapter 7.9.1

EPM-S405: Chapter 7.9.2

bySampling_CH1 ... _CH4

BYTE

Conversion time channel 1 ... 4

• see system manual "I/O system 1000":

EPM-S404: Chapter 7.9.1

EPM-S405: Chapter 7.9.2

bLimitAlarm_CH1 ... _CH4

BOOL

TRUE Activate limit value monitoring channel 1 ... 4

nUpperLimit_CH1 ... _CH4

BYTE

Upper limit value channel 1 ... 4

nLowerLimit_CH1 ... _CH4

BYTE

Lower limit value channel 1 ... 4