Function library "LenzeIo1000Drv"

Function blocks

L_io1000ParPDO610 - Communication settings PDO6 ... PDO10

48

L

DMS 1.0 EN - 07/2011 - TD05

Inputs

Identifier/data type

Information/possible settings

bExecute

BOOL

FALSEÊTRUE Start parameter setting

dwHandle

DWORD

• 9400 ServoPLC: Handle created by FB L_CanInit

• Drive PLC, 9300 Servo PLC, ECS: 10

byNodeAdr

BYTE

1 ... 127 CAN node address of the I/O system

bStoreParameter

BOOL

TRUE Save parameter set at the end of the parameterisation process.

Then the NMT command "Reset Node" is sent to the I/O system.

wCobID...

_RxPDO6 ... _RxPDO10

_TxPDO6 ... _TxPDO10

WORD

Identifier

for PDO6 ... PDO10 (PLC  I/O system)

for PDO6 ... PDO10 (I/O system  PLC)

0

Automatic allocation of the identifiers ( 51)

> 0 Value of the set identifier

byTransmissionType...

_RxPDO6 ... _RxPDO10

_TxPDO6 ... _TxPDO10

BYTE

Transmission mode

for PDO6 ... PDO10 (PLC  I/O system)

for PDO6 ... PDO10 (I/O system  PLC)

0 Event-controlled
1 Time-controlled
2 Event-controlled with higher-level cycle time
3 PDO deactivated

tCycleTime...

_RxPDO6 ... _RxPDO10

_TxPDO6 ... _TxPDO10

TIME

Cycle time

for PDO6 ... PDO10 (PLC  I/O system)

for PDO6 ... PDO10 (I/O system  PLC)

0 ... 65535 Cycle time in [ms]

tInhibitTime...

_TxPDO6 ... _TxPDO10

TIME

Blocking time

for PDO6 ... PDO10 (I/O system  PLC)

0 ... 65535 Blocking time in [ms]