Function library "lenzeio1000drv – Lenze Function library LenzeIO1000Drv User Manual

Page 24

Advertising
background image

Function library "LenzeIo1000Drv"

Function blocks

L_io1000ParCounterEPMS601 - Parameterise counter

24

L

DMS 1.0 EN - 07/2011 - TD05

Inputs

Identifier/data type

Information/possible settings

bExecute

BOOL

FALSEÊTRUE Start parameter setting of the analog output module

dwHandle

DWORD

• 9400 ServoPLC: Handle created by FB L_CanInit

• Drive PLC, 9300 Servo PLC, ECS: 10

byNodeAdr

BYTE

1 ... 127 CAN node address of the I/O system

byAnalogModuleNo

BYTE

1 ... 64 Number of the analog output module

bDiagnosticAlarm

BOOL

TRUE Enable diagnostic alarm

byCnt0

InputFrequencyTrackA

BYTE

Counter 1: Input filter of digital input 1, "A1"/"pulse"

2 100 kHz
3 60 kHz
4 30 kHz
6 10 kHz
7 5 kHz
8 2 kHz
9 1 kHz

byCnt0

InputFrequencyTrackB

BYTE

Counter 1: Input filter of digital input 5, "B1"/"direction"

2 100 kHz
3 60 kHz
4 30 kHz
6 10 kHz
7 5 kHz
8 2 kHz
9 1 kHz

byCnt0AlarmFunction

BYTE

Counter 1: Process alarm

A process alarm can be triggered in case of the following events:

bits0 Reserved
bits1 Reserved

Bit 2 Counter limit overflow

bits3 Counter limit underflow
bits4 Comparison value reached

Bit 5 Final value reached
Bit 6 Reserved
Bit 7 Reserved

byCnt0CounterFunction

BYTE

Counter 1: Counting function

0 Continuous counting
1 Single counting, main counting direction is forward
2 Single counting, main counting direction is backward
3 Single counting, no main counting direction
4 Periodic counting, main counting direction is forward
5 Periodic counting, main counting directin is backward
6 Periodic counting, no main counting direction