Function library "LenzeIo1000Drv"

Function blocks

L_io1000Data15 - Process data transfer PDO1 ... PDO5

dnStatePDO1...5

_DataFromIO

DINT

Transmission status PDO1 ... PDO5 (I/O system  PLC)

0 No error
3 PDO has been deactivated
2 Process data communication is not active

-150 CAN interface of the PLC is not in the "Operational" status
-160 Error while reading out the status of the CAN interface

-1000 Error while receiving process data
-1002 Wrong handling has been transmitted to internal receive block
-1003 Wrong data length has been transmitted to the internal receive

block

-1004 Wrong identifier has been transmitted to internal receive block
-1100 PDO data in the receive memory of the PLC have been overwritten
-1101 Timeout monitoring has been activated

bFail_DataToIO

BOOL

TRUE Transmit request to the I/O system is not correct

bFail_DataFromIO

BOOL

TRUE Receive request from the I/O system is not correct

bFail_Module

BOOL

TRUE Module diagnostics is active. Emergency object indicates error.

abyPDO1...5_DataFromIO

ARRAY[1..8] OF BYTE

Received process data (I/O system  PLC)

Identifier/data type

Value/meaning