4 entering variables manually, 1 using the softplc opc tunnel, 2 using the data manager opc tunnel – Lenze PC-based Automation Industrial PC User Manual

Page 114

Advertising
background image

Industrial PC | Parameter setting & configuration

Visualisation with »VisiWinNET®«

Constellation and connection

114

L

2.5 EN - 01/2012

13.3.4

Entering variables manually

Variables can also be entered manually, as an alternative to using the Lenze Variables

Browser. Depending on the server and the connection type (local or remote), you have to

observe a special syntax. This syntax is described on the following pages.

How to enter a variable manually:

1. Open the Project Explorer.
2. Activate the variable editor by double-clicking on the desired channel in the node

VariablesChannels.

3. Select the New item from the context menu.
4. Enter the variable name in the ItemID/address input field.

• In doing this, observe the corresponding syntax!

13.3.4.1

Using the SoftPLC OPC tunnel

How to access the variables of the SoftPLC OPC tunnel:

1. Prefix the variable with PLC.PLC:.
2. Enter the variable in the form of

<CoDeSys block>.<CoDeSys variable>

.

Example: PLC.PLC:.EPMAP

13.3.4.2

Using the data manager OPC tunnel

How to access the variables of the data manager OPC tunnel:

1. Prefix the variable with DM.
2. Enter the variable in the form of

.pari<24575

minus code>d<data type>.

Example: DM.pari24572d8
If an additional reference to a subindex is provided, supplement the following

entry:
Example with subindex "S1":pari24572s1d3