8. SUSPENDING THE SYSTEM - GENERAL

Inadequate or improper suspension of the tube heater can result in collapse of
the system, property damage, and personal injury or death.

It is the installer’s responsibility to ensure that the hardware and structural sup-
ports from which the heater is suspended are sound and of adequate strength
to support the weight and expansion forces of the heater.

Consider that the heater will expand in length as much as 1/2 inch (12.5 mm) or more for every
10 ft (3 m) of system length – typically the greater the firing rate, the greater the expansion.

Refer to Sections 13 & 14

1) Survey the available structural supports, considering the system configuration and heat re-

quirements of the area to establish the optimum heater location.

a) Locating a heater directly under joists or beams, or installing supplemental steel support

rail or angle iron can substantially reduce labor and materials

2) Tube system hangers must be located: A) straight in line; B) at a common height (level);

and C) 116” (295 cm) apart.- see Figure 6 next page.

a) NOTE: It is important that the tubes in the system are installed in alignment horizontally

(level) and vertically (in line) – this will ensure system integrity

3) Hardware with a minimum 60 lb. (30 kg) work load must be used at each heater suspension

point. A #8 Jack Chain or equivalent is typically used for suspending the heater.

a) Connect to the structure using typical hardware as illustrated in FIGURE 5 (below) or by

other mechanically sound means

b) If rigid devices such as 3/8” threaded rods are used for suspension, swing joints or other

means must be provided to allow for system expansion - approximately ½ inch to 1 inch
for every 10 ft (1 cm to 2.5 cm for every 3 m) of system length.

4) Two types of hangers are provided to suspend the tube system – see FIGURES 6 & 7

a) Plate hangers support the tubes and reflectors at each end of the tube system

b) Webbed hangers support tubes and reflectors at each tube junction

HOOK OR EYE

BOLT THROUGH

HOLE IN BEAM

BEAM CLAMP

WITH HOOK OR

EYE

HOOK OR

EYE

SCREW

PIPE RING

OR CLEVIS

HANGER

BAR-JOIST

CLAMP

FIGURE 5 TYPICAL MOUNTING HARDWARE

NOTE: It is the installer’s responsibility to ensure that mounting hardware and
fastening to structure are of sufficient strength to support the system.