Schwank STW-JZ1 User Manual

Page 36

Advertising
background image

36

STW-JZ / IW I&O Manual

IM101229

RL: 12A- BA

RD: DEC 2010

Each tube heater requires 120V, 60 HZ electrical power sized for 145VA. The heater includes
a 24V/120V relay switch . Maximum power flow for internal 24V burner components is 21VA.

The heater must be electrically grounded in accordance with the National Electrical Code.
ANSI / NFPA 70 or current Canadian Electrical code CSA C22.1.

A maximum night set-back of 9°F (5°C) is recommended for optimum economy and comfort.
To maintain satisfactory comfort levels do not turn off the heating system over night/weekends.

Maximum Power Flow = 21VA

18. WIRING DIAGRAM: 24V OR 120 VOLT THERMOSTAT OPERATION

SINGLE HEATER PER THERMOSTAT
(Multiple Heaters per Thermostat—next page)

Advertising