STW-JZ / IW I&O Manual

IM101229

RL: 12A- BA

RD: DEC 2010

TABLE 1 MINIMUM CLEARANCES TO COMBUSTIBLES*

FIGURE 1 MINIMUM CLEARANCES TO COMBUSTIBLES* - refer to Table 1 for values

*The clearance to combustible materials represents the minimum distance that must be main-

tained between the heater and a nearby surface. The stated clearance to combustibles
represents a surface temperature of 90F° (50C°) above room temperature.
.

NOTE that in the above table the clearances are measured from the reflector.

It is the installer’s responsibility to ensure that building materials with a low heat toler-

NOTE: A ‘PEEL & STICK’ SIGN IS SUPPLIED: USE AN INDELIBLE MARKER TO

ENTER VALUES ‘H’, ‘S’, ‘F’, & ‘B’ ON THE SIGN.

POST THE SIGN ADJACENT TO THE HEATER THERMOSTAT OR IN A
PROMINENT LOCATION.

See next page for details.

F

D

B

A

S

S

C

Suspended at an
angle up to 45°

Suspended
horizontally

C

FLOOR

H

T

H

M a x i m u m
Stack Height
H = T- C

‘T’ is meas-
ured on site,

FLOOR

T

M a x i m u m
Stack Height
H = T- C

‘T’ is meas-
ured on site,

MODEL

SUSPENDED AT AN ANGLE

UP TO 45 DEGREES

SUSPENDED

HORIZONTALLY

D

inches (cm)

B

inches (cm)

F

inches (cm)

C

inches (cm)

A

inches (cm)

S

inches (cm)

C

inches (cm)

STW-JZ/IW 200 13

(33)

6 (15.2) 74

(188)

70

(178)

14 (36)

44 (112)

76

(193)

STW-JZ/IW 175 12

(31)

6 (15.2)

72

(183)

68

(172)

13 (33)

42 (107)

74

(188)

STW-JZ/IW 155 5.5

(14)

1 (2.5)

44

(112)

64

(163)

3.5 (9)

19 (48)

64

(163)

STW-JZ/IW 130 4.5

(11)

1 (2.5)

35 (89)

60

(152)

3.3 (9)

11 (28)

60

(152)

STW-JZ/IW 110 3.5 (9)

1 (2.5)

26 (66)

54

(137)

2 (5)

10 (25)

54

(137)

STW-JZ/IW 80 3 (8)

1 (2.5)

23 (59)

38 (97)

1.75 (5)

6 (15)

38 (97)

STW-JZ/IW 60 2.5 (6)

1 (2.5)

17 (43)

34 (86)

1.5 (4)

5.5 (14)

34 (86)

STW-JZ/IW 45 2.75 (7)

1 (2.5)

24 (61)

32 (81)

2.25 (6)

7 (18)

32 (81)