STW-JZ / IW I&O Manual

IM101229

RL: 12A- BA

RD: DEC 2010

NOTE: Access to the manifold pressure test port is on the top of the valve. A 3/16" Allen
Wrench is necessary to check this. When checking or setting the manifold pressure, a water
manometer
should be used. Gauges which measure in ounces per square inch or pounds
per square inch are not accurate enough to properly measure or set the pressure.

THIS HEATER WILL EXPAND IN LENGTH AS IT HEATS UP. It is a normal
condition that during heat-up and cool-down a tube heater will expand and con-
tract. Allowances for heater expansion must be made in the gas connection, vent-
ing and combustion air ducting. Improper installation, alteration, or adjustment
can result in property damage, injury or death. See also Section 13

The Btuh input and the tube length determine the overall expansion that occurs.
A typical infrared tube installation will expand toward both the Burner and the
vent end.

To allow heater expansion the gas supply must be installed using:

In the USA: a stainless steel Flexible Gas Connector certified for use on an

infrared radiant tube heater (ANSI Z21.24 CSA 6.10);

in CANADA: a Type 1 Hose Connector (CAN/CGA 8.1). Also the flue vent,

and combustion air intake (if used) must be installed in such a manner that
the normal expansion of the heater will be accommodated.

TABLE 5

WARNING

Input

Rating

Btuh

Tube

Length

Feet

Approx.

Expansion

in Length

USA: Mandatory

Flexible Gas Connector

ID x Length - Part #

CANADA: Mandatory

Type ‘1’ Gas Hose

Size - Part #

45,000

10

1”

1/2” x 24” - JL-0771-XX

1/2” x 36” - JL-0771-RC

45,000

20

1 1/4”

1/2” x 24” - JL-0771-XX

1/2” x 36” - JL-0771-RC

60,000

20 / 30

1 1/2”

1/2” x 24” - JL-0771-XX

1/2” x 36” - JL-0771-RC

80,000

20 / 30 / 40

1 3/4”

1/2” x 24” - JL-0771-XX

1/2” x 36” - JL-0771-RC

110,000

30 / 40 / 50

2”

1/2” x 24” - JL-0771-XX

1/2” x 36” - JL-0771-RC

130,000

30 / 40 / 50

2”

1/2” x 24” - JL-0771-XX

1/2” x 36” - JL-0771-RC

155,000

40 / 50 / 60

2 1/2”

3/4” x 36” - JL-0771-YY

3/4” x 36” - JL-0771-RB

175,000

50 / 60 / 70

2 3/4”

3/4” x 36” - JL-0771-YY

3/4” x 36” - JL-0771-RB

200,000

50

2 3/4”

3/4” x 36” - JL-0771-YY

3/4” x 36” - JL-0771-RB

200,000

60 / 70

3 1/4”

3/4” x 36” - JL-0771-YY

3/4” x 36” - JL-0771-RB

IMPORTANT: See next page: orientation of connection between heater and gas supply.