Schwank STW-JZ1 User Manual

Page 40

Advertising
background image

40

STW-JZ / IW I&O Manual

IM101229

RL: 12A- BA

RD: DEC 2010

MAIN BURNER LIGHTS

SYSTEM RUNS UNTIL CALL FOR HEAT
ENDS

CALL FOR HEAT ENDS:

SYSTEM SHUTS OFF

TROUBLESHOOTING ENDS

 CHECK FOR STRONG SPARK AT IGNITER........

 (SEE PREVIOUS PAGE).

 CHECK FOR 24 VAC ACROSS GAS VALVE.
 CHECK OUTPUT VOLTAGE FROM CONTROL TER-

MINALS TO GAS VALVE.....IF NO VOLTAGE RE-
PLACE CONTROL.

 CHECK ELECTRICAL WIRING, AND VOLTAGE BE-

TWEEN IGNITION CONTROL AND GAS VALVE.

 IF OK, REPLACE GAS VALVE.

NOTE: IF IGNITION CONTROLS GOES INTO A
LOCKOUT, INTERRUPT POWER AND RESTART.

 CHECK CONTINUITY OF SENSOR CABLE AND

GROUND WIRE AS A POOR GROUND COULD RE-
SULT IN ERRATIC BEHAVIOUR AND NUISANCE
SHUTDOWNS EVEN THOUGH OPERATION IS NOR-
MAL AT THE TIME OF CHECKOUT.

 CHECK FOR EXCESSIVE HEAT AT SENSOR INSU-

LATOR AS TEMPERATURES ABOVE 1000°F(538°C)
CAUSES SHORT TO GROUND.

 CHECK FLAME SIGNAL IN SERIES WITH THE

GROUND AND MODULE FOR A MINIMUM 1.5UA.

 IF SIGNAL IS LOWER CHANGE IGNITER.
 IF CHECKS ARE OK.....REPLACE CONTROL.

 CHECK TEMPERATURE CONTROLLER.
 CHECK FOR FAULTY WIRING, REMOVE GAS

VALVE LEAD AT CONTROL ,

 IF VALVE CLOSES, RECHECK THE TEMPERATURE

CONTROLLER AND WIRING.

 IF VALVE STAYS OPEN....REPLACE GAS VALVE

SPARK STOPS WHEN BURNER LIGHTS

CONTROL IS NOT SENSING FLAME WITHIN THE
21 SECOND TFI AND IS STILL TRYING TO LIGHT

 CHECK CONTINUITY OF SENSOR CABLE AND

GROUND WIRE

 CHECK BURNER FLAME IS COVERING SENSOR.
 CHECK FLAME SIGNAL IN SERIES WITH THE

GROUND AND MODULE FOR 1.5UA MINIMUM.

 IF SIGNAL IS LOWER CHANGE IGNITER.
 IF CHECKS ARE OK.......REPLACE CONTROL.

NO

YES

NO

YES

YES

YES

NO

NO