Installation, Horizontal terminations – Regency Horizon HZ40E Medium Gas Fireplace User Manual

Page 23

Advertising
background image

Regency Horizon™ HZ40E-2 Gas Fireplace

23

INSTALLATION

Vent Guard

(Part #946-506/P)

Notes:

1) Liner sections should be continuous without any

joints or seams.

2) Only Flex pipe purchased from Regency

®

may be

used for Flex installations

3) Horizontal vent must be supported every 3 feet.

4) Regency

®

Direct Vent System (Flex) is only approved

for horizontal terminations.

5) Flex system can only be used up to a maximum

continuous vent length of up to 10 feet. If longer
runs are required, rigid pipe must be used.

HORIZONTAL TERMINATIONS

FLEX VENT 4" X 6-7/8

"

These venting systems, in combination with the HZ40E Direct Vent Gas Fireplace, has been tested and listed as a direct vent heater system by Warnock
Hersey/ Intertek. The location of the termination cap must conform to the requirements in the Vent Terminal Locations diagram in "Exterior Vent Termination
Locations" section.

Regency

®

Direct Vent (Flex) System Termination Kits includes all the parts needed to install the HZ40E using a fl exible vent.

FPI Kit #

Length

Contains:

#946-513

2 Feet

1) 6-7/8”

fl exible outer liner (Kit length)

2) 4”

fl exible inner liner (Kit length)

3) spring

spacers

4) thimble
5)

AstroCap termination cap

6) screws
7)

tube of Mill Pac

8) plated

screws

9)

S.S. screws #8 x 1-1/2” drill point

#946-515

4 Feet

#946-516

10 Feet