Installation, Horizontal terminations – Regency Horizon HZ40E Medium Gas Fireplace User Manual

Page 25

Advertising
background image

Regency Horizon™ HZ40E-2 Gas Fireplace

25

INSTALLATION

Maximum

36"(914mm)

Minimum

6"(152mm)

Straight Out Horizontal Venting

Diagram 1

Please note the minimum centerline for
basic install shown above.

HORIZONTAL TERMINATIONS

RIGID PIPE 4" X 6-5/8

"

The diagrams below shows examples of horizontal termination arrangements using one, two, or three 90

o

elbows (two 45

o

elbows equal one 90

o

elbow)

1) A maximum of three 90

o

elbows are permitted (not including the starting 45

o

elbow at the fl ue collar when using rigid venting).

2) Minimum distance between elbows is 1 ft. (305mm).

• Maintain clearances to combustibles as listed in the "Clearances" section.
• Horizontal vent must be supported every 3 feet.
• Firestops are required at each fl oor level and whenever passing through a wall.
• Must use optional rigid pipe adaptor (Part# 510-994) when using rigid pipe vent systems.
• A vent guard should be used whenever the termination is lower than the specifi ed minimum or as per local codes.

Flex system can only be used up to 10 feet - otherwise rigid venting must be used.

CL

CL

Min.

height

(Rigid)

36-1/4"

(743mm)

center

of hole