Installation, Venting arrangements - vertical terminations – Regency Horizon HZ40E Medium Gas Fireplace User Manual

Page 33

Advertising
background image

Regency Horizon™ HZ40E-2 Gas Fireplace

33

VENTING ARRANGEMENTS - VERTICAL TERMINATIONS

with Co-linear Flex System for both
Residential & Manufactured Homes

into Masonry Fireplaces

The shaded area in the diagrams show

the allowable vertical terminations when

using two- 3" co-linear aluminium fl ex

and 4 x 6-5/8" rigid pipe.

8

'

(2.4m) Min.

36-1/4

(921mm)

35

'

(10.7m) Max.

35

Horizontal Distance (Feet)

V

ertical Height (feet)

Vent Restrictor

Set 2

Vent Restrictor

V

ent Restrictor

V

V

ent Restrictor

Set 2

Set 1

16' Max. V

ent

8' (2.4m) Min.

Horizontal Distance (Feet)

V

ertical Height (feet)

2’

(51mm) max.

35

36-1/4”

(921mm)

35' (10.7m) Max.

Vent Restrictor

Set 2

16' Max.

V

ent Restrictor Set 1

Restrictor Set 1

Restrictor Set 2

35

Horizontal Distance (Feet)

V

ertical Height (feet)

2’

(51mm) max.

Combined min. of 8

’(2.4m).

6’

(152mm) max.

Combined max. of

.

35' (10.7m) Max.

36-1/4”

(921mm)

Vent Restrictor

Set 2

Combined max. of

16' Max.

V

ent Restrictor Set 1

Restrictor Set 1

Restrictor Set 2