Rockwell Automation 1395 DC Drive, 800-1250 Hp, FRN 5.XX-9.30 User Manual
Page 107
Chapter 5
Programming Parameters
5-16
Parameter 100 – Logic Status [Logic Status]
Internal Units : None
Programming Terminal units : Bit Field
Description : This is a word of status data that indicates conditions
within the Drive in boolean logic. Where a bit is set to 1, the
corresponding condition in the drive is true, otherwise the condition is
false. The bits in the Logic Status word are defined as:
Fault Field 0
Fault Field 1
Active Logic Command 0
Active Logic Command 1
Contactor Closed
Drive Running
Running Reverse
Ready
At Current Limit
At Set Speed
At Zero Speed
At Speed 1
At Speed 2
At Speed 3
At Speed 4
At Speed 5
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
N O T C H A N G E A B L E
Bit #
DHT REF. BITS
DEFINITIONS
Fault Field 0, 1 (Bits 0, 1) : This 2-bit field denotes the fault status of
the Drive as follows:
Flt. Fld. 1
0
0
1
1
Flt. Fld. 0
0
1
0
1
DEFINITION
No Fault
Warning Fault
Soft Fault
Hard Fault
Active Logic Command 0,1 (Bits 2,3) : This 2-bit field denotes the
logic command the Drive is acting upon as follows:
Logic CMD 1
0
1
1
Logic CMD. 0
1
0
1
DEFINITION
Parm 150
Parm 151
Parm 152