Chapter 4
Installation

4-8

As previously explained, two different types of grounds are used in the
1395 drive. They are defined as follows:

Safety Ground (PE) – A Safety Ground is normally required by the
electrical code and is defined externally as PE ground. Main PE is located
on the bottom of the cabinet on the left side .

Signal Ground (TE) – The Signal Ground point is used for all control
signals internal to the drive. Depending on the application, TE may be
connected to a system TE bus or connected to PE ground. TE is located on
the bottom of the cabinet

Table 4.B
Signal Ground (TE)

Wiring Connection

TE – Bus

400 – 600 HP 230VAC
700 – 1250 HP 460VAC
1000 – 2000 HP 660VAC

Rating

Table 4.C
Safety Ground (PE) Connections

Ground Terminal

PE – Bus

Rating

400 – 600 HP 230VAC
700 – 1250 HP 460VAC
1000 – 2000 HP 660VAC