Rockwell Automation 1395 DC Drive, 800-1250 Hp, FRN 5.XX-9.30 User Manual

Page 153

Advertising
background image

Chapter 5
Programming Parameters

5-62

Parameter 717 – Process Trim Low Limit [Proc Trim Lo Lim]

Internal units : 1000h = 4096 = 1 PU
Programming Terminal units: None
Minimum Value: –32767
Maximum Value: +32767
Default Value: –4096
Description: The output of the process trim regulator is limited by
adjustable high and low limits. This parameter specifies the low limit
of the Process Trim output value .

Parameter 718 – Process Trim High Limit [Proc Trim Hi Lim]

Internal units : 1000h = 4096 = 1 PU
Programming Terminal units: None
Minimum Value: –32767
Maximum Value: +32767
Default Value: +4096
Description: The output of the Process Trim regulator is limited by
adjustable high and low limits. This parameter specifies the high
limit of the Process Trim output value.

Parameter 719 – Process Trim Output Gain [Proc Trim Out K]

Internal units : 800h = 2048 = unity gain
Programming Terminal units: None
Minimum Value: –16.00
Maximum Value: +16.00
Default Value: 1.0 (unity gain)
Description: The output of the Process Trim regulator is scaled by a
gain factor. This occurs immediately before the application upper &
lower limit. This parameter specifies the gain value to use. Positive
or negative gains may be used. A negative gain value will invert the
Process Trim output.

Parameter 720 – Overload Pending Level [Ovld Pend Level]

Internal units : 4096 = 1000H = 100% rated motor current
Programming Terminal units: percent of rated motor current
Minimum Value: 0.024%
Maximum Value: 260%
Default Value: 115%
Description: This parameter determines the armature current level at
which an overload pending fault will occur.

Advertising