Chapter 4
Installation

4-14

Figure 4.5
TB3 Terminal Descriptions

115V ECOAST1

20

19

18

17

16

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

TB3

Main Control

Board

Power Stage

Interface

Board

ENCA1

ENCA1

ENCB1

ENCB1

ENCPWR

ENCGND

–24V OUT

+24V OUT

–24V ECOAST

+24V ECOAST

READY 2

READY 1

115V COMMON OUT

115V ECOAST2

RESET IN

MOTOR TEMP IN

COMMON IN

Encoder

Drive Ready Output

115V AC Common

115V AC E-Coast

Reset*

Motor Thermostat**

24VDC or

115VAC Voltage

Source

Refer to Table 4.J

24V DC E-Coast

Channel A

Channel A

Channel B

Channel B

+ Supply Voltage

– Supply Voltage

*

If parameter 620 = 0, then the Reset input requires a N.O. pushbutton as shown above. Closing the
pushbutton causes System Reset to occur. This is the default value for the 1395.

*

If parameter 620 = 1, then the Normal Stop input requires a N.C. pushbutton as shown above.
Opening the pushbutton causes Normal Stop to occur.

Refer to Table 6.L

** If no thermostat is used, 115VAC or 24VDC must still be applied to TB3 terminal 2.

NOTE: If N.C. is used, and 620 = 0, Drive will be in a continuous reset condition.
If N.O. is used, and 620 = 1, A Stop will be present in Logic Cmd 1 Par.150