Circuit Board Jumper Connections

There are several jumpers located on different boards in the 1395 that are
used to configure the drive for a specific application.

1. Verify that the motor field current jumper, is in the proper location per

Table 4.F. Obtain the motor full field current data from the motor
nameplate. The position of the jumper is determined by both the drive
current rating and DC shunt field current rating. Use the drive current
rating to select the column in Table 4.F and the field current to select
the field current jumper position.

Table 4.F
Field Current Jumper Setting

J1 Jumper
on Feedback Bd.

1

2

3

4

400 – 600 HP
240VDC

42.4 A

18.5 A

8.7 A

2.4 A

700 – 1250 HP
500VDC

42.4 A

18.5 A

8.7 A

2.4 A

1000 – 2000 HP
700VDC

42.4 A

18.5 A

8.7 A

2.4 A

2. Verify that the voltage selection for the Reset and Motor Thermostat

inputs is correct. Jumpers J11 and J12 on the Power Stage Interface
Board determine whether the voltage used for the Reset and Motor
Thermostat inputs is 24VDC or 115VAC. Both switches should be in
the same position (See Table 4.G).

Table 4.G
Power Stage Interface Board Jumper Settings

Jumper

Position

Purpose

J11

J12

1 – 2

2 – 3

1 – 2

2 – 3

115VAC Motor Thermoguard Input

24VDC Motor Thermoguard Input

115VAC Motor Reset Input

24 VDC Motor Reset Input