OC_InitScanner

Library of Routines

6–47

Publication 1747-6.5.3 June 1998

Return Value:

Considerations:

Supported in the DOS API library and the Windows NT API library

Example:

HANDLE

Handle;

OCINIT

scaninit;

int

retcode;

scaninit.InputImageSize = 128;

/* 64 words for input image */

scaninit.OutputImageSize = 128;

/* 64 words for output image */

scaninit.HostRetentiveDataSize = 500;

/* 256 words for host data area */

retcode = OC_InitScanner( Handle, &scaninit );

Name:

Value:

Description:

SUCCESS

0

scanner was initialized successfully

ERR_OCACCESS

2

handle

does not have access to the scanner

ERR_OCMEM

3

shared memory not found

ERR_OCPAR

6

initialization failed due to invalid partition information

ERR_OCPOST

7

POST in progress or scanner POST failed, see OC_GetScannerStatus

ERR_OCREINIT

4

scanner has already been initialized

ERR_OCRESPONSE

10

scanner did not respond to request