OC_EnableForces

Library of Routines

6–15

Publication 1747-6.5.3 June 1998

OC_EnableForces

OC_EnableForces enables/disables forces for all inputs and outputs with entries in
the force files on the scanner.

Syntax:

int

OC_EnableForces(HANDLE handle, int mode);

Parameters:

Description:

If no I/O forces are in the force files, OC_EnableForces does not enable forces and instead returns an error.
All forces are disabled by default.

Return Value:

!

ATTENTION:

Enabling forces will potentially change the

output data values that your application
was previously controlling.

Parameter:

Description:

handle

Must be a valid handle returned from OC_OpenScanner

mode

If

mode

is:

FORCE_ENABLE

forces are enabled

FORCE_DISABLE

forces are disabled

FORCE_CLEAR

forces are disabled and all input and

output forces

are cleared from the force files.

Name:

Value:

Description:

SUCCESS

0

forces were updated successfully

ERR_OCACCESS

2

handle

does not have access to scanner

ERR_OCNOFORCES

15

no forces installed, scanner cannot enable forces

ERR_OCPARAM

8

parameter contains invalid value

ERR_OCRESPONSE

10

scanner did not respond to request

ERR_OCSCANCFG

14

scanner has not been configured