Installing the dos api, Checking led indicators -5 status -5, Installing the dos api -5 – Rockwell Automation 1747-PCINT API Software for 1746 I/O User Manual

Page 13: Checking led indicators status

Advertising
background image

Overview

1–5

Publication 1747-6.5.3 June 1998

If a non-recoverable fault occurs, reset the scanner (cycle power). Some possible
non-recoverable faults include:

POST failure

background diagnostic failure

internal watchdog timeout

Checking LED Indicators

STATUS

The STATUS indicator reports the status of the scanner. The following table lists
the LED states for STATUS:

Installing the
DOS API

To install the DOS API, copy the following files to a directory you create. The
sample code files are optional, but they show how to use the API functions.

This state:

Means:

Take this action:

Yellow

The scanner is running POST.

None

Flashing green

The scanner is in idle mode and is
not scanning I/O.

None

Solid green

The scanner is scanning I/O.

None

Flashing red

An I/O fault has occurred.

Check software to identify
fault condition.

Solid red

A scanner internal fault has
occurred.

Power system off and back on. If
the problem persists, service may
be required.

Off

The adapter is not powered up.

Turn on power.

PCI INTERFACE

STATUS

BATT

LED 1

LED 2

LED 3

LED 4

This file:

Contains:

ocapil.lib

API functions that you link to your application

ocapi.h

API header file that contains API-referenced structures

sample.c

Sample application program calling the API functions

sampleb.mak

Sample make file for the Borland C compiler

samplem.mak

Sample make file for the Microsoft C compiler

Advertising
This manual is related to the following products: