Rockwell Automation 1747-PCINT API Software for 1746 I/O User Manual

Page 149

Advertising
background image

Error Codes

A–3

Publication 1747-6.5.3 June 1998

The error code data provides information specific to the cause of all extended errors,
except 0xF0 (see Table A.3). The first byte of the error code data contains a
subsystem identifier.

Table A.3

First Byte of Error Code Data - Scanner Communications Subsystem Error Codes

The second byte of the error code data provides details about the subsystem
identifier.

Table A.4

Second Byte of Error Code Data - Scanner Communications Subsystem Error Codes

The third byte of the Error Code Data provides details about the Subsystem
Error Codes.

Table A.5

Third Byte of Error Code Data - Backplane Interface Subsystem Error Codes

Subsystem ID:

Description:

0x06

Scanner Communications

0x08

Backplane Interface (module I/O)

Error Code:

Description:

0x00

Download error - invalid directory file pointer block

0x01

Download error - change to Idle mode failed

0x02

Download error - configuration file CRC failed (byte 1 contains
the file number)

0x03

Download error - directory CRC failed

0x04

Download error - input or output image exceeds partition
allocation (byte 1 contains 0 for output image, 1 for input)

Error Code:

Description:

0x01

Rack configuration verify error

0x02

DII configuration error

0x03

I/O error occurred while updating slot enables

0x06

I/O error occurred while polling for PINT

0x07

Bad module mode change attempted

0x08

Slot error occurred during mode change

0x09

Source of module interrupt not found

0x0A

Corrupted directory file detected when going to run mode

0x0C

I/O error occurred while servicing module interrupt

0x0D

Module interrupt from disabled slot

0x0E

Interrupting module requested unsupported service

0x0F

I/O error while performing input scan

0x10

I/O error while performing output scan

0x11

Verified read or write error

Advertising