Oc_setinputupdate, Mode -67 – Rockwell Automation 1747-PCINT API Software for 1746 I/O User Manual

Page 121

Advertising
background image

OC_SetInputUpdate Mode

Library of Routines

6–67

Publication 1747-6.5.3 June 1998

OC_SetInputUpdate
Mode

OC_SetInputUpdateMode controls how the scanner updates inputs.

Syntax:

int

OC_SetInputUpdateMode(HANDLE handle, int mode);

Parameters:

Description:

This function does not affect output image scanning.

Return Value:

Considerations:

Supported in the DOS API library and the Windows NT API library

Example:

HANDLE

Handle;

int

retcode;

retcode = OC_SetInputUpdateMode( Handle, INUPD_NEVER );

/* Must use OC_DemandInputScan() function to obtain new input data */

Parameter:

Description:

handle

Must be a valid handle returned from OC_OpenScanner

mode

If

mode

is:

INUPD_NEVER

the scanner does not scan inputs unless explicitly
requested by the OC_DemandInputScan function.

INUPD_ALWAYS

the scanner continuously updates inputs on
every scan.

By default, the input update mode is INUPD_ALWAYS. A change in status
of the input update mode takes effect at the start of the next scan.

Name:

Value:

Description:

SUCCESS

0

conditional scan was set successfully

ERR_OCACCESS

2

handle

does not have access to scanner

ERR_OCINIT

5

scanner has not been initialized; see OC_InitScanner

ERR_OCPARAM

8

parameter contains invalid value

Advertising