OC_GetStatusFile

Library of Routines

6–37

Publication 1747-6.5.3 June 1998

0/6

status

Forces installed bit
This bit is set is forces have been installed.

0/7 to 0/12

reserved

0/13

dynamic configuration

Major error halted bit
This bit is set by the scanner when a major error is encountered. The
scanner enters a fault condition. Word 2, Fault Code will contain a code
which can be used to diagnose the fault condition.
When bit 0/13 is set, the scanner places all outputs in a safe state and
sets the Status LED to the fault state (flashing red).
Once a major fault state exists, the condition must be corrected and bit 0/
13 cleared before the scanner will accept a mode change request.

0/14

reserved

0/15

status

First pass bit
The bit is set by the scanner to indicate that the first I/O scan following
entry into Scan mode is in progress. The scanner clears this bit following
the first scan.

1/0 to 1/10

reserved

1/11

status

Battery low bit
This bit is set by the scanner when the Battery Low LED is on. It is cleared
when the Battery Low LED is off.

1/12

status

DII overflow bit
This bit is set by the scanner when a DII interrupt occurs and the scanner
is unable to successfully transmit the DII Received priority message to the
host.

1/13 to 1/15

reserved

2

status

Major error fault code
A code is written to this word by the scanner when a major error occurs.
See word S:0/13. The code defines the type of fault. If not zero, the upper
byte indicates the slot associated with the error. This word is not cleared
by the scanner.

3 to 4

dynamic configuration

I/O slot enables
These two words are bit mapped to represent the 30 possible I/O slots in
an SLC 500 system. Bits 3/0 through 4/14 represent slots 0-30 (slot 0 is
reserved for the 1746 I/O PCI Interface). Bit 4/15 is unused.
When a bit is set (default condition), it allows the I/O module in the
referenced slot to be updated in the I/O scan. When a bit is cleared, the
corresponding I/O module will no longer be included in the I/O scan.
Changes to the I/O slot enable bits will take affect at the end of the next
I/O scan.

5

status

Maximum observed scan time
This word indicates the maximum observed interval between consecutive
I/O scans. The interval time is reported in units of 250 ms.
Resolution of the observed scan time is +0 to -250 ms. For example, the
value 10 indicates that 2.25-2.5 ms was the longest scan time.

6

dynamic configuration

Index register
This word indicates the element offset used in indexed addressing.

7 to 8

status

I/O interrupt pending
These two words are bit-mapped to the 30 I/O slots. Bits 7/1 through 8/
14 refer to slots 1-30. Bits 7/0 and 8/15 are not used.
The pending bit associated with a slot is set when an interrupt request is
received from that slot. This bit is set regardless of the state of the I/O
interrupt enabled bit (wee word 9 and 10).

Word/Bit:

Classification:

Description: