Rockwell Automation 1747-PCINT API Software for 1746 I/O User Manual

Page 105

Advertising
background image

OC_PollScanner

Library of Routines

6–51

Publication 1747-6.5.3 June 1998

The data returned in the

MsgData

member array depends upon the value in

MsgID

:

Separate queues hold messages received from each source. The host application must call OC_PollScanner
periodically to read messages from each enabled source to prevent messages from being discarded. If a
message queue is full when a new message is received, the oldest message is discarded and the next call to
OC_PollScanner results in a return value of ERR_OCOVERRUN. The queue can hold as many as
five messages.

Return Value:

Considerations:

Supported in the DOS API library and the Windows NT API library

Example:

HANDLE

Handle;

MSGBUF

msgbuf;

int

retcode;

retcode = OC_PollScanner( Handle, OCMSG_ANY, &msgbuf );

/* Check msgbuf.MsgID for what message is available */

This

MsgID

:

Returns:

MsgID=OCMSG_IOINT

MsgData[0]

slot number that generated the interrupt

MsgID=OCMSG_DIINT

MsgData[0

]

mask of last bit transition that generated the interrupt

MsgData[2

]

lowbyte of count of matches that generated the interrupt

MsgData[3]

highbyte of count of matches that generated the interrupt

MsgID=OCMSG_EOS_DMDIN

MsgID=OCMSG_EOS_DMDOUT
MsgID=OC_EOS

MsgData[0]

number of scans that occurred since the last end-of-scan

message of this type was read

Name:

Value:

Description:

SUCCESS

0

scanner was polled successfully

ERR_OCACCESS

2

handle

does not have access to scanner

ERR_OCOVERRUN

16

a message has been discarded

Advertising
This manual is related to the following products: