Oc_getmeasuredscan, Time -30 – Rockwell Automation 1747-PCINT API Software for 1746 I/O User Manual

Page 84

Advertising
background image

6–30

Library of Routines

OC_GetMeasuredScan Time

Publication 1747-6.5.3 June 1998

OC_GetMeasuredScan
Time

OC_GetMeasuredScanTime returns the maximum and last observed I/O scan times.

Syntax:

int

OC_GetMeasuredScanTime(HANDLE Handle, WORD *maxtime, WORD *lasttime);

Parameters:

Description:

The scanner calculates these values at the end of each I/O scan. The values are represented in units of 250
microseconds.

The scan times are reset to zero when changing to Scan mode, and are not valid until the end of the second
I/O scan. Only the timed I/O scans are measured; the demand input or output scans are not.

Return Value:

Considerations:

Supported in the DOS API library and the Windows NT API library

Example:

HANDLE

Handle;

WORD

max_time, last_time;

int

retcode;

retcode = OC_GetMeasuredScanTime( Handle, &max_time, &last_time );

Parameter:

Description:

handle

Must be a valid handle returned from OC_OpenScanner

maxtime

Returns the maximum scan time

lasttime

Returns the last scan time

Name:

Value:

Description:

SUCCESS

0

measured scan time was read successfully

ERR_OCACCESS

2

handle

does not have access to scanner

ERR_OCINIT

5

scanner has not been initialized, see OC_InitScanner

Advertising