OC_SetScanMode

Publication 1747-6.5.3 June 1998

OC_SetScanMode

OC_SetScanMode changes the scan mode of the scanner.

Syntax:

int

OC_SetScanMode(HANDLE handle, int mode);

Parameters:

Description:

The scanner must be properly configured before going to Scan mode.

OC_SetScanMode will fail if there are any unread extended errors or faults. Call OC_GetExtendedError to
extract all extended errors and call OC_ClearFault to clear any faults before calling OC_SetScanMode.

Before the scanner changes to Scan mode, it compares the downloaded I/O configuration to the racks and
I/O modules actually installed. If there are any problems, an extended error is generated and
OC_SetScanMode returns an error. If the scanner finds no problems, the scanner is in Scan mode when this
function returns.

Return Value:

Considerations:

Supported in the DOS API library and the Windows NT API library

Example:

HANDLE

Handle;

int

retcode;

retcode = OC_SetScanMode( Handle, SCAN_RUN ); /* Scan I/O */

Parameter:

Description:

handle

Must be a valid handle returned from OC_OpenScanner

mode

If

mode

is:

SCAN_IDLE

the scanner changes to Idle mode and stops

scanning I/O
SCAN_RUN

the scanner changes to Scan mode and begins
scanning I/O.

Name:

Value:

Description:

SUCCESS

0

scan mode was set successfully

ERR_OCACCESS

2

handle

does not have access to the scanner

ERR_OCFAULT

13

scanner is faulted

ERR_OCINIT

5

scanner has not been initialized, see OC_InitScanner

ERR_OCPARAM

8

parameter contains invalid value

ERR_OCRESPONSE

10

scanner did not respond to request