OC_CreateIO Configuration

Library of Routines

6–7

Publication 1747-6.5.3 June 1998

OC_CreateIO
Configuration

OC_CreateIOConfiguration creates a scanner configuration from an application-
specific installation of rack sizes and installed modules. See chapter 5 for more
information.

Syntax:

int

OC_CreateIOConfiguration(OCIOCFG *iocfg);

Parameters:

Description:

Modules can be specified by name or by mix and type. The function automatically fills in the rest of the
required information in the

OCIOCFG

structure.

This function returns in

iocfg

the scanner configuration information obtained from the rack sizes and

installed module types specified in

iocfg

. The scanner configuration can then be downloaded to the scanner

with OC_DownloadIOConfiguration, which allows the application to control the number of racks and their
sizes and the position and type of modules installed in the racks.

The

OCIOCFG

structure is defined as:

typedef struct tagOCIOCFG
{

BYTE

Rack1Size;

/* number of slots in Rack 1 */

BYTE

Rack2Size;

/* number of slots in Rack 2 */

BYTE

Rack3Size;

/* number of slots in Rack 3 */

OCSLOTCFG SlotCfg[OCMAXSLOT];/* configuration for each slot */

} OCIOCFG;

Return Value:

Considerations:

Supported in the DOS API library and the Windows NT API library

Parameter:

Description:

iocfg

Specifies the rack sizes and installed modules

Name:

Value:

Description:

SUCCESS

0

I/O configuration was read successfully

ERR_OCUNKNOWN

18

at least one module was not found in the internal database
The

SlotCfg

data for the unknown module is not altered; the remaining

modules are configured.