Channel step response -6, Channel step response – Rockwell Automation 1746-NT8 SLC 500 Thermocouple/mV Analog Input Module User Manual User Manual

Page 36

Advertising
background image

Publication 1746-UM022B-EN-P - January 2005

3-6 Considerations Before Using Your Module

Signal Attenuation with 60 Hz Input Filter

Signal Attenuation with 250 Hz Input Filter

Channel Step Response

The channel filter frequency determines the channel’s step response.
The step response is time required for the analog input signal to reach
95% of its expected, final value given a full-scale step change in the
input signal. This means that if an input signal changes faster than the
channel step response, a portion of that signal will be attenuated by
the channel filter. The table on page 3-4 shows the step response for
each filter frequency.

0

-20

-40

-60

-80

-100

-120

-140

-160

-180

-200

0

60

120

180

240

300

360 Hz

-3 dB

15.7 Hz

Signal Frequency

Amplitude (in dB)

0

-20

-40

-60

-80

-100

-120

-140

-160

-180

-200

0

250

500

750

1000

1250

1500 Hz

-3 dB

Amplitude (in dB)

Signal Frequency

65.5 Hz