Module specifications, Electrical specifications, Appendix a – Rockwell Automation 1746-NT8 SLC 500 Thermocouple/mV Analog Input Module User Manual User Manual

Page 81: Appendix

Advertising
background image

1

Publication 1746-UM022B-EN-P - January 2005

Appendix

A

Module Specifications

This appendix lists the specifications for the 1746-NT8
Thermocouple/millivolt Input Module.

Electrical Specifications

Backplane Current Consumption

120 mA at 5V dc
70 mA at 24Vdc

Backplane Power Consumption

2.28W maximum (0.6W at 5V dc, 1.68W at 24V dc)

Number of Channels

8 (backplane and channel-to-channel isolated)

I/O Chassis Location

Any I/O module slot except 0

A/D Conversion Method

Sigma-Delta Modulation

Input Filtering

Input Filtering Low pass digital filter with
programmable notch (filter) frequencies

Normal Mode Rejection (between [+]
input and [-] input)

Greater than 100 dB at 50/60 Hz

Common Mode Rejection (between
input and ground)

Greater than 100 dB at 50/60 Hz

Input Filter Cut-Off Frequencies

2.6 Hz at 10 Hz filter frequency

13.1 Hz at 50 Hz filter frequency

15.72 Hz at 60 Hz filter frequency

65.5 Hz at 250 Hz filter frequency

Greater than 100 dB at 50/60 Hz

Calibration

Module autocalibrates at power-up and
approximately every two minutes afterward

Input Over-voltage Protection

±30V dc continuous 600W pulsed for 1 ms.

Isolation

500V dc for 1 minute between inputs and chassis
ground and between inputs and backplane. 12.5V
dc continuous between channels.

Advertising