Programming Examples 5-5

B3:6

4

CHECKING_CJC

EN

DN

TON

Timer On Delay
Timer

T11:1

Time Base

1.0

Preset

7<

Accum

0<

TON

CJC_CFG_TMR

T11:1

DN

CJC_CFG_TMR/DN

OSR

B3:0

4

MOV

Move
Source

I:1.0

3744<

Dest

N10:12

329<

MOV

CJC_TEMP

T11:1

DN

CJC_CFG_TMR/DN

MOV

Move
Source

N10:0

-32767<

Dest

O:1.0

-32767<

MOV

NT8_CONFIGURATION

EN

DN

TON

Timer On Delay
Timer

T11:2

Time Base

1.0

Preset

7<

Accum

0<

TON

REG_CFG_TMR

T11:2

DN

REG_CFG_TMR/DN

U

B3:6

4

CHECKING_CJC

END

0005

0009

0008

0007

0006

Wait 7 seconds for Channel 0 to accept CJC configuration and provide a data value (time

depends on module configuration).

Copy CJC Temperature (I:1.0) into CJC register (N10:12)

Move Channel 0’s regular configuration word into the Channel 0 configuration word and start timer to

ensure word has been accepted prior to taking the thermocouple temperature readings.

When CJC check cycle is completed (T1 1:2/DN is set), reset the Checking CJC Bit (B3/100).