Troubleshooting flowchart – Rockwell Automation 1746-NT8 SLC 500 Thermocouple/mV Analog Input Module User Manual User Manual

Page 78

Advertising
background image

Publication 1746-UM022B-EN-P - January 2005

6-6 Troubleshooting Your Module

Troubleshooting Flowchart

End.

mV

End.

No

Yes

Bit 15

set 1

Bit 12

set (1)

Bit 14

set (1)

Bit 13

set (1)

Is problem

corrected?

No

Yes

Yes

No

End .

Yes

No

Thermocouple

Check LEDs
on module.

Module Status

LED(s) off.

Module Status

LED(s) off.

Channel

Status LED(s)

flashing.

Channel

Status LED(s)

off.

Channel

Status LED(s)

on.

Channel

is not enabled.

Channel

is enabled and

working.

Module fault

condition.

Normal

module

operation.

Fault

condition.

Enable channel if

desired by setting

channel config.

word (bit 0=1).

Retry.

Check to see that

module is seated

properly in

chassis. Cycle

power.

Are

faulted channel(s)

configured for mV

or thermocouple

input?

Is more than

one LED

blinking?

CJC fault has

probably

occurred.

Check channel

status words bits

12 through 15.

Check that wiring is secure

at both CJCs and that the

temperature within the

enclosure is in the range
limits of the CJC sensor.

Channel error. Check

configuration word bits 1

through 4 for valid input

type configuration and

ensure bits 12 through 14

are set to zero. Retry.

Over-range condition exists.

The input signal is greater

thank the high scale limit for

the channel or the CJC

connections. Corret and

retry.

Under-range condition

exists. The input signal is

less than the low scale limit

for the channel or the CJC

connections. Correct and

retry.

An open-circuit condition

is present. Check channel

and CJC wiring for open or

loose connections. Retry.

Contact your local

Allen-Bradley

distributor.

Contact your local

Allen-Bradley

distributor.

Contact your local

Allen-Bradley

distributor.

Is problem
corrected?

Is problem
corrected?

Advertising