Input specifications – Rockwell Automation 1746-NT8 SLC 500 Thermocouple/mV Analog Input Module User Manual User Manual

Page 83

Advertising
background image

Publication 1746-UM022B-EN-P - January 2005

Module Specifications A-3

Input Specifications

Type of Input (Selectable)

Thermocouple Type J -210°C to +760°C

(-346°F to +1400°F)

Thermocouple Type K -270°C to +1370°C

(-454°F to +2498°F)

Thermocouple Type T -270°C to +400°C

(-454°F to +752°F)

Thermocouple Type E -270°C to +1000°C

(-454°F to +1832°F)

Thermocouple Type R 0°C to +1768°C

(+32°F to +3214°F)

Thermocouple Type S 0°C to +1768°C

(+32°F to +3214°F)

Thermocouple Type B +300°C to +1820°C

(+572°F to +3308°F)

Thermocouple Type N 0°C to +1300°C

(+32°F to +2372°F)

Millivolt (-50mV dc to +50mV dc)

Millivolt (-100mV dc to +100mV dc)

Thermocouple Linearization

NIST ITS-90 standard

Cold Junction Compensation

Accuracy ±1.72°C, -25°C to +105°C

Module Input Impedance

Greater than 10MW

Input Device Impedance

Output impedance of input device must be less than 100 ohm to meet
accuracy specifications.

Temperature Scale (Selectable)

°C or °F and 0.1°C or 0.1°F

DC Millivolt Scale (Selectable)

0.1 mV or 0.01 mV

Open Circuit Detection (Selectable)

Upscale, Downscale, Zero, or Disabled

Time to Detect Open Circuit

One channel cycle time

Input Step Response

0 to 95% in 400 ms (10 Hz)

Display Resolution

See Channel Data Word Resolution table on page 4-8

Overall Module Accuracy at 257°C (77°F)

See Module Accuracy Tables, page A-6

Overall Module Accuracy

See Module Accuracy Tables, page A-6

Overall Module Drift

See Module Accuracy Tables, page A-6

Module Update Time

Dependent upon enabled channels (see Update Time, page 3-7)

Channel Turn-Off Time

Up to one module update time