Programming Examples 5-7

calibration time to ensure that the new input data matches the channel
configuration requested. The above table shows how to calculate the
update time and auto-calibration time for the channel configuration
being used.

Interfacing to the PID
Instruction

The thermocouple module was designed to interface directly to the
SLC 5/02 or later processor PID instruction without the need for an
intermediate scale operation.

Example - Use 1746-NT8 channel data as the process variable in the
PID instruction.

1. Select scaled-for-PID as the data type in the channel

configuration word.

2. Specify the thermocouple channel data word as the process

variable for the PID instruction.

In this example, the value -32701 (8043 H) is the numeric equivalent
of configuration word N10:0 for channel 0. It is configured for a type
K thermocouple, scaled-for-PID, zero the signal for an open-circuit,
10 Hz, °C, and channel enabled.

Programming for PID Control Example

MOV
MOVE
Source N10:0

-32701

Dest O:3.0

0

s:1
] [
15

PID
PID
Control Block

N11:0

Process Variable

I:3.0

Control Variable

N11:23

Control Block Length

23

SCL
SCALE
Source N11:23

Rate [/10000]

Offset

Dest

First Pass Bit

Initialize NT8

Channel 0

Rung 2:0

Rung 2:1

Rung 2:2

The Rate and Offset parameters should be set per your application.
The Destination will typically be an analog output channel.