Publication 1746-UM022B-EN-P - January 2005

Channel Configuration, Data, and Status 4-13

Explanations of the status conditions follow.

Channel Status (Bit 0)

The channel status bit indicates operational state of the channel.
When the channel enable bit is set in the configuration word, the
thermocouple module configures the selected channel and takes a
data sample for the channel data word before setting this bit in the
status word.

Input Type Status (Bits 1 through 4)

The input type bit field indicates what type of input signal you have
configured for the channel. This field reflects the input type defined in
the channel configuration word.

Channel filter
frequency

10 Hz input filter

0

0

50 Hz input filter

0

1

60 HZ input filter

1

0

250 Hz input filter

1

1

Open-circuit
error

No error

0

Open circuit detected

1

Under-range
error

No error

0

Under range condition

1

Over-range
error

No error

0

Over range condition

1

Channel error No error

0

Channel error

1

Channel 0 to 7 Status Word (I:e.0 through I:e.7) - Bit Definitions

To Select

Make these bit settings

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

TIP

It takes one timing cycle to complete an update.
(Refer to Chapter 3 for module update times.)

IMPORTANT

If the channel for which you are seeking status is
disabled, all bit fields are cleared. The status word
for any disabled channel is always 0000 0000 0000
0000 regardless of any previous setting that may
have been made to the configuration word.