Led troubleshooting tables -3, Led troubleshooting tables – Rockwell Automation 1746-NT8 SLC 500 Thermocouple/mV Analog Input Module User Manual User Manual

Page 75

Advertising
background image

Publication 1746-UM022B-EN-P - January 2005

Troubleshooting Your Module 6-3

LED Troubleshooting Tables

Module-status LED

If Module Status
LED is:

Then:

Take this Corrective Action:

On

The module is
operating properly.

No action required.

Off

The module is
turned off, or it
detected a module
fault.

Cycle power. If the condition persists, call
your local Allen-Bradley distributor for
assistance.

Flashing

Jumper may be in
wrong position.

Check jumper 1 position.

Module-status and Channel-status LED

If Module
Status
LED is:

And Channel
Status LED
is:

Then:

Take this Corrective Action:

On

On

The channel is enabled. No action required.

Flashing

The module detected:
open-circuit condition,
under-range condition,
over-range condition.

Examine error bits in status word
If bit 12=1, the input has an open
circuit
If bit 13=1, the input value is
under range
If bit 14=1, the input value is over
range
If bit 15=1, the channel has a
diagnostic channel error

Off

The module is in power
up, or the channel is
disabled.

No action is required.