4-8 Channel Configuration, Data, and Status

1746-NT8 Thermocouple Module - Channel Data Wo

r

d

Format

1746-NT8 Thermocouple Module - Channel Data Word Resolution

Data Format

Input Type

Engineering Units x10

Engineering Units x1

Scaled for PID Proportional

Counts

°Celsius

°Fahrenheit

°Celsius

°Fahrenheit

J

-210 to +760

-346 to +1400

-2100 to +7600

-3460 to +14000

0 to +16383

-32768 to +32767

K

-270 to +1370

-454 to +2498

-2700 to +13700

-4540 to +24980

0 to +16383

-32768 to +32767

T

-270 to +400

-454 to +752

-2700 to +4000

-4540 to +7520

0 to +16383

-32768 to +32767

E

-270 to +1000

-454 to +1832

-2700 to +10000

-4540 to +18320

0 to +16383

-32768 to +32767

R

0 to +1768

+32 to +3214

0 to +17680

+320 to+32140

0 to +16383

-32768 to +32767

S

0 to +1768

+32 to +2372

0 to +17680

+320 to +32140

0 to +16383

-32768 to +32767

B

+300 to +1820

+572 to +3308

+3000 to +18200

+5720 to +3276.7

(2)

0 to +16383

-32768 to +32767

N

0 to +1300

+32 to +2372

0 to +13000

+320 to +23720

0 to +16383

-32768 to +32767

±50 mV

(1)

-500 to +500

-500 to +500

-5000 to +5000

-5000 to +5000

0 to +16383

-32768 to +32767

±100 mV

(1)

-1000 to +1000

-1000 to +1000

-10000 to +1000

-10000 to +10000

0 to +16383

-32768 to +32767

CJC Sensor

-25 to +105

-13 to +221

-250 to +1050

-130 to +2210

0 to +16383

-32768 to +32767

(1) When millivolts are selected, the temperature setting is ignored. Analog input data is the same for either °C or °F selection.

(2) Type B thermocouple cannot be represented in engineering units x1 (°F) above 3276.7°F. Software treats it as an over range error.

Data Format

Input
Type

Engineering Units x10

Engineering Units x1

Scaled for PID

Proportional Counts

°Celsius

°Fahrenheit °Celsius

°Fahrenheit °Celsius

°Fahrenheit

°Celsius

°Fahrenheit

J

1°C/step

1°F/step

1°C/step

1°F/step

0.0592°C/step

0.1066°F/step 0.0148°C/step 0.0266°F/step

K

1°C/step

1°F/step

1°C/step

1°F/step

0.1001°C/step

0.1802°F/step 0.0250°C/step 0.0450°F/step

T

1°C/step

1°F/step

1°C/step

1°F/step

0.0409°C/step

0.0736°F/step 0.0102°C/step 0.0184°F/step

E

1°C/step

1°F/step

1°C/step

1°F/step

0.0775°C/step

0.1395°F/step 0.0194°C/step 0.0349°F/step

R

1°C/step

1°F/step

1°C/step

1°F/step

0.1079°C/step

0.1942°F/step 0.0270°C/step 0.0486°F/step

S

1°C/step

1°F/step

1°C/step

1°F/step

0.1079°C/step

0.1942°F/step 0.0270°C/step 0.0486°F/step

B

1°C/step

1°F/step

1°C/step

1°F/step

0.0928°C/step

0.1670°F/step 0.0232°C/step 0.0417°F/step

N

1°C/step

1°F/step

1°C/step

1°F/step

0.0793°C/step

0.1428°F/step 0.0198°C/step 0.0357°F/step

±50 mV

(1)

0.1mV/step 0.1mV/step

0.1mV/step

0.1mV/step

6.104µV/step

6.104µV/step

1.526µV/step

1.526µV/step

±100 mV

(1)

0.1mV/step 0.1mV/step

0.1mV/step

0.1mV/step

12.21µV/step

12.21µV/step

3.052µV/step

3.052µV/step

CJC
Sensor

1°C/step

1°F/step

1°C/step

1°F/step

0.0079°C/step

0.0143°F/step 0.0020°C/step 0.0036°F/step

(1) When millivolts are selected, the temperature setting is ignored. Analog input data is the same for either °C or °F selection.