Isolation – Rockwell Automation 1746-NT8 SLC 500 Thermocouple/mV Analog Input Module User Manual User Manual

Page 94

Advertising
background image

Publication 1746-UM022B-EN-P - January 2005

B-2 Using Grounded Junction, Ungrounded Junction, and Exposed Junction Thermocouples

Grounded Junction

Ungrounded (Insulated) Junction

Exposed Junction

Isolation

The 1746-NT8 module provides the following electrical isolation:

12.5V dc electrical isolation channel-to-channel

500V dc electrical isolation channel-to-chassis ground

500V dc electrical isolation channel-to-backplane

Care must be taken when choosing a thermocouple type and
connecting it to the 1746-NT8 module from the environment being
measured. If adequate precautions are not taken for a given
thermocouple type, the electrical isolation of the 1746-NT8 module
may be compromised.

Extension Wire

Metal Sheath

Measuring Junction is
connected to sheath

Measuring Junction is
isolated from sheath

Measuring Junction
has no sheath