Page 44

Advertising
background image

Publication 1746-UM022B-EN-P - January 2005

4-4 Channel Configuration, Data, and Status

A detailed explanation appears in the following table:

Channel Configuration Word (0:e.0 through 0:e.7) - Bit Definitions

To Select

Make these bit settings

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

Channel
Enable

Channel Disable

0

Channel Enable

1

Input
Type

Thermocouple J

0

0

0

0

Thermocouple K

0

0

0

1

Thermocouple T

0

0

1

0

Thermocouple E

0

0

1

1

Thermocouple R

0

1

0

0

Thermocouple S

0

1

0

1

Thermocouple B

0

1

1

0

Thermocouple N

0

1

1

1

-50 to +50 mV

1

0

0

0

-100 to +100 mV

1

0

0

1

Invalid

1

0

1

0

Invalid

1

0

1

1

Invalid

1

1

0

0

Invalid

1

1

0

1

Invalid

1

1

1

0

CJC temperature

1

1

1

1

Data
Format

Engineering Units x 1

(1)

0

0

Engineering Units x 10

(1)

0

1

Scaled-for-PID

1

0

Proportional counts

1

1

Open Circuit

Zero on open circuit

0

0

Max. on open circuit

0

1

Min. on open circuit

1

0

Disabled

1

1

Temperature
units

°C

(2)

0

°F

(2)

1

Channel
filter
frequency

10 Hz input filter

0

0

50 Hz input filter

0

1

60 HZ input filter

1

0

250 Hz input filter

1

1

Unused

Unused

(3)

0

0

0

Invalid

1

1

1

Input Image
Type

Status Word

0

Data Word

1

(1) For engineering units x 1, values are expressed in 0.1 degrees or 0.01 mV. For engineering units x 10, values are expressed in 1.0 degrees or 0.1 mV.

(2) When millivolt input type is selected, the bit setting for temperature units is ignored.

(3) Ensure unused bits 12 through 14 are always set to zero.