Publication 1746-UM022B-EN-P - January 2005

5-14 Programming Examples

S:1

15

step

U

B3:0

4

NT8_CONFIGURED

B3:0

4

NT8_CONFIGURED

MVM

Masked Move
Source

N30:2

256<

Mask

0FH

15<

Dest

N11:3

0<

MVM

RIO_RACK1_FLT

NEQ

Not Equal
Source A

N11:3

0<

Source B

0

0<

NEQ

RIO_RACK1_FLT

U

B3:0

4

NT8_CONFIGURED

B3:0

4

NT8_CONFIGURED

BT20:1

EN

NT8_BTW/EN

EN

DN

ER

BTW

Block Transfer Write
Module Type Generic Block Transfer
Rack

001

Group

0

Module

0

Control Block

BT20:1

Data File

N12:10

Length

8

Continuous

No

BTW

NT8_BTW

BT20:1

DN

BTW_DONE

L

B3:0

4

NT8_CONFIGURED

B3:0

4

NT8_CONFIGURED

BT20:0

EN

BTR_TRIGGER

EN

DN

ER

BTR

Block Transfer Read
Module Type Generic Block Transfer
Rack

001

Group

0

Module

0

Control Block

BT20:0

Data File

N12:0

Length

8

Continuous

No

BTR

END

During the first scan, clear the NT8 Configurated bit (B3/4) to initiate the NT8 configuration process.
First scan or SFC

If the NT8 is configured and a rack fault occurs, clear the NT8 Configured bit (B3/4) to initiate the NT8 configuration process.

Until the NT8 is configured, send the 8 configuration words (N12:10 - 17) to the NT8 using repeating BTW’s.

If the NT8 is configured, read the 8 input words into N12:0 - N12:7 using repeating BTR’s.

When the NT8 is configured latch the NT8 Configured bit (B3/4).