Configuration

About This Chapter

This chapter describes the various configuration options that you can use to
set up assembly connections.

Configure the Connection

This connection is accepted with or without a configuration assembly present.
If a configuration assembly is present, it must contain the following minimum
information.

Chassis Size

Before establishing I/O connections, you must configure the 1734 adapters
for chassis size. This ensures that the correct number of modules are present
in the chassis at power up. The chassis size must include 1 count for the
adapter (Chassis Size = number of I/O modules + 1).

Minimal Adapter Configuration Assembly

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

Config 0

Reserved (Set to 0)

Config 1

Reserved (Set to 0)

Config 2

Reserved (Set to 0)

Config 3

Reserved (Set to 0)

Config 4

Chassis size (Low Byte)

Config 5

Chassis size (High Byte)

Config 6

Alignment for Produced Assembly (T

O)

Config 7

Size per slot (T

O) (in Bytes)

Config 8

Alignment for Consumed Assembly (O

T)

Config 9

Size per slot (O

T) (in Bytes)