Rockwell Automation 1738 Assembly Connections for POINT I/O and ArmorPOINT I/O EtherNet/IP Adapters User Manual

Page 26

Advertising
background image

Publication 1734-UM016A-EN-P - October 2010

20 Using an Assembly Connection

and consumed alignment choice is Double Word alignment which is
enumerated as a 4. See the following table for valid alignment values.

Add I/O Module Configuration

If individual module configuration is required, it can be appended to
the configuration header. In the example shown below a 1734-OB4E module
is being configured. Byte 10 indicates that the data is to be sent to slot 2. Byte
11 specifies the size of the data as 8 bytes. Bytes 12 and 13 specify the OB4E
module configuration assembly instance 0x7B. The instance number is entered
in little endian (least significant byte first). In byte 16 the value of 7 indicates
that when the module is in Idle mode, Hold Last State should be enabled for
channels 0, 1, and 2 but not channel 3. If more module configuration is
needed, it could begin at byte 22 with the slot number of the next module to
be configured.

Alignment choices for configuration header

Alignment Choice

Value

Byte

0

Word

2

Double Word

4

Fixed size per slot

0xFF

Advertising