Rockwell Automation 1738 Assembly Connections for POINT I/O and ArmorPOINT I/O EtherNet/IP Adapters User Manual
Page 51
Publication 1734-UM016A-EN-P - October 2010
1734/1738 I/O Module Assembly Information 45
Eight-channel Configurable Discrete Input/Output Modules
All eight channel "configurable" discrete I/O modules use the same
configuration and I/O assemblies. Use the tables shown below for the
following modules:
• 1734-8CFG
• 1738-8CFGM12
• 1738-8CFGM23
• 1738-8CFGM8
Produced Diagnostic Data Assembly 101
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
Reserved
Fault LED
State
Fault 12…15
Fault 8…11
Fault 4…7
Fault 0…3
Consumed Output Data Assembly 37
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
Ch 7
Ch 6
Ch 5
Ch 4
Ch 3
Ch 2
Ch 1
Ch 0
1
Ch 15
Ch 14
Ch 13
Ch 12
Ch 11
Ch 10
Ch 9
Ch 8
Configuration Assembly Instance 103
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
Input Off to On Filter Low Byte
1
Input Off to On Filter High Byte
2
Input On to Off Filter Low Byte
3
Input On to Off Filter High Byte
4
Fault Action 7
Fault Action 6
Fault Action 5
Fault Action 4
Fault Action 3
Fault Action 2
Fault Action 1
Fault Action 0
5
Fault Action 7
Fault Action 6
Fault Action 5
Fault Action 4
Fault Action 3
Fault Action 2
Fault Action 1
Fault Action 0
6
Idle Action 7
Idle Action 6
Idle Action 5
Idle Action 4
Idle Action 3
Idle Action 2
Idle Action 1
Idle Action 0
7
Idle Value 7
Idle Value 6
Idle Value 5
Idle Value 4
Idle Value 3
Idle Value 2
Idle Value 1
Idle Value 0
Produced Input Data Assembly 4
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
Ch 7
Ch 6
Ch 5
Ch 4
Ch 3
Ch 2
Ch 1
Ch 0