Publication 1734-UM016A-EN-P - October 2010

1734/1738 I/O Module Assembly Information 45

Eight-channel Configurable Discrete Input/Output Modules

All eight channel "configurable" discrete I/O modules use the same
configuration and I/O assemblies. Use the tables shown below for the
following modules:

• 1734-8CFG
• 1738-8CFGM12
• 1738-8CFGM23
• 1738-8CFGM8

Produced Diagnostic Data Assembly 101

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

Reserved

Fault LED
State

Fault 12…15

Fault 8…11

Fault 4…7

Fault 0…3

Consumed Output Data Assembly 37

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

Ch 7

Ch 6

Ch 5

Ch 4

Ch 3

Ch 2

Ch 1

Ch 0

1

Ch 15

Ch 14

Ch 13

Ch 12

Ch 11

Ch 10

Ch 9

Ch 8

Configuration Assembly Instance 103

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

Input Off to On Filter Low Byte

1

Input Off to On Filter High Byte

2

Input On to Off Filter Low Byte

3

Input On to Off Filter High Byte

4

Fault Action 7

Fault Action 6

Fault Action 5

Fault Action 4

Fault Action 3

Fault Action 2

Fault Action 1

Fault Action 0

5

Fault Action 7

Fault Action 6

Fault Action 5

Fault Action 4

Fault Action 3

Fault Action 2

Fault Action 1

Fault Action 0

6

Idle Action 7

Idle Action 6

Idle Action 5

Idle Action 4

Idle Action 3

Idle Action 2

Idle Action 1

Idle Action 0

7

Idle Value 7

Idle Value 6

Idle Value 5

Idle Value 4

Idle Value 3

Idle Value 2

Idle Value 1

Idle Value 0

Produced Input Data Assembly 4

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

Ch 7

Ch 6

Ch 5

Ch 4

Ch 3

Ch 2

Ch 1

Ch 0