Publication 1734-UM016A-EN-P - October 2010

70 1734/1738 I/O Module Assembly Information

The format and length of the Produced and Consumed I/O assemblies vary
with the configuration of the module. For more information regarding the
specific fields of these assemblies and how they are impacted by the
configuration, refer to the product user manual.

15

ASCII Consume String Data Type

16

ASCII Transmit Swap Mode

17

Transmit Handshake Mode

Produced Input Data Assembly 101

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

RX Transaction ID

1

Status

2

Reserved or Length

(2)

(2)

The meaning of these fields depends on the configuration of the module.

3

Reserved or Length

(2)

4

ASCII Data (from 1 to 128 bytes)

N

(1)

(1)

The length of the assembly depends on the amount of ASCII Data transmitted.

<CR> Terminator

Consumed Output Data Assembly 102

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

Reserved

1

TX Transaction ID

2

Reserved

3

Length

4

ASCII Data (from 1 to 128 bytes)

N

(1)

(1)

The length of the assembly depends on the amount of ASCII Data transmitted.

<CR> Terminator