Two-channel discrete output modules with status – Rockwell Automation 1738 Assembly Connections for POINT I/O and ArmorPOINT I/O EtherNet/IP Adapters User Manual
Page 43
Publication 1734-UM016A-EN-P - October 2010
1734/1738 I/O Module Assembly Information 37
Two-channel Discrete Output Modules with Status
All two-channel "enhanced" discrete output modules use the same
configuration and I/O assemblies. Use the tables shown below for the
following modules:
• 1734-OB2E or 1738-OB2E
• 1734-OV2E or 1738-0V2E
• 1734-OB2EP or 1738-OB2EP
Produced Input Data Assembly 4
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
Ch 7
Ch 6
Ch 5
Ch 4
Ch 3
Ch 2
Ch 1
Ch 0
Configuration Assembly Instance 123
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
Reserved
Fault State 1
Fault State 0
1
Reserved
Fault Value 1
Fault Value 0
2
Reserved
Idle State 1
Idle State 0
3
Reserved
Idle Value 1
Idle Value 0
4
Reserved
Enable No Load 1
Enable No Load 0
5
Reserved
Reset mode 1
Reset mode 0
6
Reserved
Enable Latched Alarms 1
Enable Latched Alarms 0
7
Pad
Produced Input Data Assembly 42
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
Reserved
Ch 1
Status
Ch 0
Status
Consumed Output Data Assembly 32
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
Reserved
Ch 1
Ch 0