Rockwell Automation 1738 Assembly Connections for POINT I/O and ArmorPOINT I/O EtherNet/IP Adapters User Manual
Page 48
Publication 1734-UM016A-EN-P - October 2010
42 1734/1738 I/O Module Assembly Information
This POINT I/O input module produces 1 or 2 bytes of input data based on
which produced assembly is selected. The default assembly (instance 101) is 2
bytes. This module does not consume I/O data.
Configuration Assembly Instance 103
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
Input 0 Off to On Filter Low Byte
1
Input 0 Off to On Filter High Byte
2
Input 0 On to Off Filter Low Byte
3
Input 0 On to Off Filter High Byte
4
Input 1 Off to On Filter Low Byte
5
Input 1 Off to On Filter High Byte
6
Input 1 On to Off Filter Low Byte
7
Input 1 On to Off Filter High Byte
8
Input 2 Off to On Filter Low Byte
9
Input 2 Off to On Filter High Byte
10
Input 2 On to Off Filter Low Byte
11
Input 2 On to Off Filter High Byte
12
Input 3 Off to On Filter Low Byte
13
Input 3 Off to On Filter High Byte
14
Input 3 On to Off Filter Low Byte
15
Input 3 On to Off Filter High Byte
16
Autobaud
Disable
Enable Open
Wire Detect 3
Enable Open
Wire Detect 2
Enable Open
Wire Detect 1
Enable Open
Wire Detect 0
17
Produced Assembly Instance
Produced Diagnostic Input Data Assembly 101
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
Fault 3
Fault 2
Fault 1
Fault 0
Input 3
Input 2
Input 1
Input 0
1
Short
Circuit 3
Short
Circuit 2
Short
Circuit 1
Short
Circuit 0
Off
Wire 3
Off
Wire 2
Off
Wire 1
Off
Wire 0
Produced Input Data Assembly 23
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
Fault 3
Fault 2
Fault 1
Fault 0
Input 3
Input 2
Input 1
Input 0