Publication 1734-UM016A-EN-P - October 2010

42 1734/1738 I/O Module Assembly Information

This POINT I/O input module produces 1 or 2 bytes of input data based on
which produced assembly is selected. The default assembly (instance 101) is 2
bytes. This module does not consume I/O data.

Configuration Assembly Instance 103

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

Input 0 Off to On Filter Low Byte

1

Input 0 Off to On Filter High Byte

2

Input 0 On to Off Filter Low Byte

3

Input 0 On to Off Filter High Byte

4

Input 1 Off to On Filter Low Byte

5

Input 1 Off to On Filter High Byte

6

Input 1 On to Off Filter Low Byte

7

Input 1 On to Off Filter High Byte

8

Input 2 Off to On Filter Low Byte

9

Input 2 Off to On Filter High Byte

10

Input 2 On to Off Filter Low Byte

11

Input 2 On to Off Filter High Byte

12

Input 3 Off to On Filter Low Byte

13

Input 3 Off to On Filter High Byte

14

Input 3 On to Off Filter Low Byte

15

Input 3 On to Off Filter High Byte

16

Autobaud
Disable

Enable Open
Wire Detect 3

Enable Open
Wire Detect 2

Enable Open
Wire Detect 1

Enable Open
Wire Detect 0

17

Produced Assembly Instance

Produced Diagnostic Input Data Assembly 101

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

Fault 3

Fault 2

Fault 1

Fault 0

Input 3

Input 2

Input 1

Input 0

1

Short
Circuit 3

Short
Circuit 2

Short
Circuit 1

Short
Circuit 0

Off
Wire 3

Off
Wire 2

Off
Wire 1

Off
Wire 0

Produced Input Data Assembly 23

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

Fault 3

Fault 2

Fault 1

Fault 0

Input 3

Input 2

Input 1

Input 0