1734/1738 I/O Module Assembly Information 49
default produced assembly. For more information regarding the specific fields
of these assemblies, consult the product's user manual.
Configuration Assembly Instance 123
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
Counter Configuration
1
Filter Selection
2
Decimal Position
3
Reserved
4
Time Base (low byte)
5
Time Base (high byte)
6
Gate Interval
7
Scalar
8
Rollover Value [Low Byte]
9
Rollover Value [1]
10
Rollover Value [2]
11
Rollover Value [High Byte]
12
Preset Value [Low Byte]
13
Preset Value [1]
14
Preset Value [2]
15
Preset Value [High Byte]
16
Counter Control SSV
17
Reserved (set to 0)
Produced Input Data Assembly 102
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
Stored Channel Data [Low Byte]
1
Stored Channel Data [1]
2
Stored Channel Data [2]
3
Stored Channel Data [High Byte]
4
Status (Low Byte)
5
Status (High Byte)
Consumed Output Data Assembly 105
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
Counter Control