Module assembly information, Discrete modules, Chapter 5 – Rockwell Automation 1738 Assembly Connections for POINT I/O and ArmorPOINT I/O EtherNet/IP Adapters User Manual
Page 37: 1734/1738 i/o module assembly information, Chapter
31
Publication 1734-UM016A-EN-P - October 2010
Chapter
5
1734/1738 I/O Module Assembly Information
Module Assembly
Information
Discrete Modules
POINT I/O and ArmorPOINT I/O Discrete I/O modules
Cat. No
Description
Configuration
Assembly
Instance
Configuration
Size
Produced Size
Consumed Size
1734-IB2
1738-IB2
2 point DC sink input
103
8
1
0
1734-IB4
1738-IB4
4 point DC sink input
103
16
1
0
1734-IB4D
1738-IB4D
2 point DC sink input with diagnostics
103
18
2,1
0
1734-IB8
1738-IB8
8 point DC sink input
103
32
1
0
1734-IV2
2 point DC source input
103
8
1
0
1734-IV4
1738-IV4
4 point DC source input
103
16
1
0
1734-IV8
1738-IV8
8 point DC source input
103
32
1
0
1734-OB2E
1738-OB2E
2 point DC source output
123
8
1
1
1734-OB4E
1738-OB4E
4 point DC source output
123
8
1
1
1734-OB2
2 point DC source output
123
8
1
(1)
1
1734-OB4
4 point DC source output
123
8
1
1
1734-OB8
8 point DC source output
123
8
1
1
1734-OB8E
1738-OB8E
8 point DC source output
123
8
1
1
1734-OW2
2 point relay output
103
4
0
1
1734-OW4
1738-OW4
4 point relay output
103
4
0
1
1734-OV2E
2 point 24V DC sink output
123
8
1
1
1734-OV4E
1738-OV4E
4 point 24V DC sink output
123
8
1
1
1734-OV8E
8 point 24V DC sink output
123
8
1
1
1734-OX2
2 point Form C Relay output
103
4
0
1